ESP MAG2 2 Zone Programmable Fire Panel - Metal Casing

  • 2 programmable zones
  • Active end of line monitoring and head removal
  • 30 fire detectors per zone
  • Unlimited number of call points per zone
  • Integral evacuate alarm button
  • 'Class change' facility
  • Enable/disable security key
  • One man walk test facility
  • Volt free fire change over relay
  • Volt free fault change over relay
  • Individual sounder circuit fault ID
  • Individual zone/sounder isolate
  • BS5839 and EN54 P2/4 compliant
  • CE certified
  • Requires only 1x12v battery
  • Metal casing
SKU
MAG2
Excl. VAT £71.99
£86.39 Incl. VAT
Inputs
Max Detectors Per Zone 30
Thresholds for Zone Conditions 0 - 2 mA (Fault condition) 2 - 6 mA (Normal condition) 6 - 110 mA (Fire condition) 110 mA - Short (Fault condition)
Power
Mains Fail Consumption 50mA
Mains Supply 230 VAC ± 10%
Standby Supply 1 x 7ah 12V S.L.A. Battery
Power Availability 0.7 amps
Outputs
Sounder 1 24V (max 300mA fused)
Sounder 2 24V (max 300mA fused)
Fault/Fire Relay Volt free 500mA @ 24V (max load)
Auxiliary Output 24VDC (300mA fused)
Environment
Working Temperature 0 to 40ºC
Storage Temperature -20 to 60ºC
Humidity 0 - 95%
Dimensions MAG2 200 x 290 x 80mm
Weight MAG2 - 2.7Kg
More Information
Dimensions 200mm x 290mm x 80mm
Write Your Own Review
Only registered users can write reviews. Please Sign in or create an account